List of operating data, special ranges

Special operating data
Order
Plain text
code
required
Y00
N=.
Y10
TV=.
D=
Y11
RL=.
Y20
RL1=.
RL2=.
Y30
MA=.
ME=.
D=
Y31
MA=.
ME=.
Y32
MA=.
ME=.
D=
Y50
T63=.
S= .
Y60
Y61
S=.
Y70
UG=.
OG=.
H=.
K=
A=
T=.
SITRANS TW
A5E00054075-05
Options
Factor N for multiplication with the charac-
teristic values of resistance thermometers
Range of values: 0.10 to 10.00
1. Example: 3 x Pt500 parallel:
N = 5/3 = 1.667;
2. Example: Ni120: N = 1.2
Temperature TV of the fixed cold junction
Dimension; range of values: C, K, F, R
Line resistance RL in : for compensation of
cold junction line of external Pt100
DIN IEC 751
Range of values: 0.00 to 100.00
Line resistances RL of channel 1 (RL1) and
channel 2 (RL2) in : if the resistance ther-
mometer or the resistance-based sensor is
connected in a two-wire system
Range of values depending on type of sen-
sor: 0.00 to 100.00
Start-of-scale value MA and full-scale value
ME for thermocouples and resistance ther-
mometers
(Range of values depending on type of sen-
sor)
Dimension, range of values: C, K, F, R)
Start-of-scale value MA and full-scale value
ME for resistance-based sensors or potenti-
ometers in :
Range of values: 0.00 to 6,000.00
Start-of-scale value MA and full-scale value
ME for mV, V, μA and mA sources
Range of values depending on type of sen-
sor: -120.00 to 1,000.00
Dimension (mV entered as MV, V as V,
μA as UA, mA as MA)
Response time T63 of software filter in s
Range of values: 0.0 to 100.0
Safety value S of signal output in mA or in V
corresponding to the set type of output.
Range of values
- with current output: -0.50 to 23.00
- with voltage output: -0.25 to 10.75
Safety value S with line breakage of sensor
Safety value S with line breakage or short-
circuit of sensor
Lower limit value (dimension as defined by
measuring range)
Upper limit value (dimension as defined by
measuring range)
Hysteresis (dimension as defined by mea-
suring range)
Switch on/off combination of limit function
and sensor fault detection; J=on; N=off
(standard: J)
Type of relay output: A=open-circuit opera-
tion; R=closed-circuit operation (standard: R)
Switching delay T of relay output in s
Range of values: 0.0 to 10.0 (standard: 0.0)
Temperature Measurement
Transmitters for rail mounting
four-wire system, universal, HART
Ordering data