All screw-type connectors are mechanically coded at the factory to prevent
confusing them (figure 20, page 128). The connector coding also ensures:
−
Input circuit: Incorrect connection of screw-type connectors for Ex circuits
and non-Ex circuits is prevented.
−
Power supply: Incorrect connection of screw-type connectors to a power
supply not suitable for the device is prevented.
•
The specified data for the electrical connection (Chapter 5, page 117) must be
observed.
Mains
connection
1 - 4
: Measuring input (wiring variations, see Chapter 6.4, page 129)
5 - 6
: Analog output (U or I output can be parameterized by plug-in jumpers, see Chapter 3.5.3, page 92)
7 - 8
: Connection of HART communication for on-site parameterization
9 - 11
: Output sensor error / limit value alarm as a relay contact (parameterization behavior see below or
Chapter 3.3, page 90)
12
: PE conductor connection
13 - 14
: Input power supply (reverse polarity protected)
Figure 19
Wiring diagram input, outputs, power supply
Relay output:
•
Idle current principle (relay opens in case of error)
−
Device switched off
−
Device switched on and no error
−
Device switched on and error
•
Open circuit principle (relay closes in case of error)
−
Device switched off
−
Device switched on and no error
−
Device switched on and error
SITRANS TW
A5E00054075-05
GWM
Relay output
Installation and commissioning
Sensor
: Terminals 10 and 11 connected
: Terminals 9 and 11 connected
: Terminals 10 and 11 connected
: Terminals 10 and 11 connected
: Terminals 10 and 11 connected
: Terminals 9 and 11 connected
127