Herunterladen Inhalt Inhalt Diese Seite drucken

Software Parameterization; Order; Current/Voltage Measurement By U/I Input Plug 7Ng3092-8Aw; Application And Use - Siemens SITRANS TW 7NG3242 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.6.3

Software parameterization

"External PT100" should be selected in the parameterization software (HART-Com-
municator or SIMATIC PDM) as the type of reference point compensation.
3.6.4

Order

Add code S02 or 23 to the order number of the SITRANS TW
Order as accessory under order number 7NG3092-8AV
3.7
Current/voltage measurement by U/I input plug
7NG3092-8AW
3.7.1

Application and use

It serves in devices with the ordering designation 7NG3242-0***0 as a measuring
set for:
voltage measurement in the measuring range:
current measurement in the measuring range:
The basic accuracy of the U/I input plug is: 0,1 %.
The minimum span is for:
voltage measurement (measuring range -1.2 to 10 V):
current measurement (measuring range -12 to 100 mA):
WARNING
The U/I input plug may not be used in hazardous (explosive) areas.
SITRANS TW
A5E00054075-05
Hardware functions
-1.2 to 10 V DC or
-12 to 100 mA DC
0.05 V
0.41 mA
95

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis