Observed fault
Red LED: 1 flash light
SB Series AIR Beam Detectors Installation Manual
Possible cause
Error in modules settings:
Several "Master" modules
are set up
No "Master" module is set
up
The position of "Slave" is
not correct
Inter-module connection
fault
Mixing of installed ranges. Verify the compatibility of modules. Put the
Solution
Verify DIP switches 3 to 5 settings. See
"Installing modules in columns" on page 17
for more details.
Set up one of the "Master" modules with the
switches 1 and 2. See "Installing modules in
columns" on page 17 for more details.
Check the position of "Slave" modules with
switches 1 and 2. See "Installing modules in
columns" on page 17 for more details.
Wire the inter-module connections. See
"Installing modules in columns" on page 17
for more details.
modules of the same range only. See
Table 7 on page 18 for more details.