5.3 Connection with the mains

Connect the SPL limiter to the mains with the supplied power supply cable. The occupation of the connection
cables is as follows:
Cable
Pin
Brown
Live
Blue
Neutral
Yellow/Green Earth
Attention! The earth has to be connected! If the device will be directly connected with the local power
supply network, a disconnection switch with a minimum opening of 3 mm at every pole has to
be included in the permanent electrical installation.
The device must only be connected with an electric installation carried out in compliance with
the IEC standards. The electric installation must be equipped with a Residual Current Device
(RCD) with a maximum fault current of 30 mA.
International
L
N
27/30
00051963.DOC, Version 1.0