Herunterladen Diese Seite drucken

ABB ACH580-04 Bedienungsanleitung Seite 14

Vorschau ausblenden Andere Handbücher für ACH580-04:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
14 EN – Quick installation and start-up instructions
Step
Task
3
Option +B051:
• Carefully step drill sufficiently big holes to the cable entry clear plastic shroud
for the cables to be connected.
• Align the holes in the vertical direction according to the alignment holes in the
shroud. Smooth the hole edges.
• Remove the plastic sheeting from both sides of the shroud.
• Attach the cables firmly to the cabinet frame to prevent chafing against the
hole edges.
4
Option +B051: Put the conductors of the input cables through the drilled holes in
the clear plastic shroud.
5
Connect the input power cable conductors to the L1/U1, L2/V1 and L3/W1 connec-
EN
tion busbars.
6
Option +B051: Move the clear plastic shroud along the input cables to its final po-
DE
sition. Install the front clear plastic shroud.
ES
7
Install the upper front cover.
FR
8
Remove the cardboard protective covering from the drive module air outlet.
9
Option +B051: Cut a hole in the side clear plastic shroud for the cable entry clear
IT
plastic shroud. Install the side and top shrouds to the drive module.
TR
Default I/O connection diagram
The default control connections for the HVAC default are shown below.
X1 Reference voltage and analog inputs and outputs
1...10 kohm
Max.
500 ohm
X2 & X3 Aux. voltage output and programmable digital inputs
Connection
1
1
2
2
3
3
4
4
5
6
5
7
6
8
7
9
8
9
10
10
11
11
12
12
13
13
14
14
15
16
15
17
16
18
17
18
Term
Description
SCR
Signal cable shield (screen)
AI1
Output frequency/speed reference:
0...10 V
AGND
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Actual feedback: 0...20 mA
AGND
Analog input circuit common
AO1
Output frequency: 0...10 V
AO2
Motor current: 0...20 mA
AGND
Analog output circuit common
+24V
Aux. voltage output +24 V DC, max. 250 mA
DGND
Aux. voltage output common
DCOM
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Not configured
DI3
Constant frequency/speed selection
DI4
Start interlock 1 (1 = allow start)
DI5
Not configured
DI6
Not configured
Figure
R
S
T
U
V

Werbung

loading