Min.
short-circuit
ACH580-04-...
current
A
585A-4
11000
650A-4
11000
725A-4
-
820A-4
-
880A-4
-
1) Minimum permitted short-circuit current of the electrical power network.
Fuses (UL)
UL fuses for branch circuit protection per NEC are listed below. Obey local regulations.
Input
ACH580-04-...
current
(A)
U
= 480 V
n
505A-4
483
585A-4
573
650A-4
623
725A-4
705
820A-4
807
880A-4
807
1.
Fuses are required as part of the installation, are not included in the base drive
configuration and must be provided by others.
2.
Fuses with a higher current rating than specified must not be used.
3.
The UL listed fuses recommended by ABB are the required branch circuit protection
per NEC. Circuit breakers listed in section Circuit breakers (UL) are also acceptable
as branch circuit protection.
4.
The recommended size or smaller UL listed 248 fast acting, time delay, or high
speed fuses must be used to maintain the UL listing of the drive. Additional
protection can be used. Refer to local codes and regulations.
5.
A fuse of a different class can be used at the high fault rating where the I
2
I
t of the new fuse is not greater than that of the specified fuse.
6.
UL listed 248 fast acting, time delay, or high speed fuses from other manufacturers
can be used if they meet the same class and rating requirements specified in the
rules above.
7.
When you install a drive, always obey ABB installation instructions, NEC
requirements and local codes.
8.
Alternative fuses can be used if they meet certain characteristics. For permitted
fuses, see
Branch Circuit Protection for ABB drives manual supplement
(3AXD50000645015).
Ultrarapid (aR) fuses, type DIN 43620 (blade style)
Input current
Nominal
1)
current
A
573
623
705
807
807
A
V
600
600
800
600
800
600
1000
600
1000
600
1000
600
Technical data and references 121
2
I
t
2
A
A
s
1600
4150000
1600
4150000
-
-
-
-
-
-
UL fuses
Manufacturer
Bussmann
Ferraz
Ferraz
Ferraz
Ferraz
Ferraz
Voltage
Fuse
rating
V
Bussmann
690
170M8557D
690
170M8557D
-
-
-
-
-
-
UL class
Type
T
JJS-600
L
A4BY800
L
A4BY800
L
A4BY1000
L
A4BY1000
L
A4BY1000
peak
EN
DE
ES
FR
IT