Terminal (21-22)
Input
U
, V
i
max
I
, I
i
max
P
i
C
i
L
i
Terminal (22–21, 21–22)
Input
U
, V
16.6 V
o
OC
I
, I
0.2 mA
o
SC
P
0.8 mW
o
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
U
m
Terminal (51, 52)
Supply
Voltage
Terminal (43, 44)
Relay Output
Voltage max.
Current max.
Power max.
Terminal (53, 54)
Status Relay
Voltage max.
Current max.
Power max.
1066530000/08/12-2018
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
30 V
120 mA
900 mW
3 nF
2 µH
Group
IIC or A, B
IIB or C, E, F
IIA or D, G
253 V, max. 400 Hz
19.2...31.2 V DC
Non Hazardous
Location
250 V AC / 30 V DC
2 A AC / 2 A DC
500 VA / 60 W
Non Hazardous
Location
125 V AC / 110 V DC
0.5 A AC / 0.3 A DC
62.5 VA / 32 W
C
L
o
o
0.4 µF
1000 mH
2.3 µF
1000 mH
9.5 µF
1000 mH
Zone 2 Installation
32 V AC / 30 V DC
2 A AC / 2 A DC
64 VA / 60 W
Zone 2 Installation
32 V AC / 32 V DC
0.5 A AC / 1 A DC
16 VA / 32 W
L
/R
o
o
25 mH/Ω
100 mH/Ω
200 mH/Ω