Herunterladen Inhalt Inhalt Diese Seite drucken

Weidmuller ACT20X Handbuch Seite 150

Inhaltsverzeichnis

Werbung

Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
Terminal (21–24, 22–24)
Input
U
, V
28 V
o
OC
I
, I
93 mA
o
SC
P
0.65 W
o
Terminal (21–23)
Input
U
, V
28 V
o
OC
I
, I
1.1 mA
o
SC
P
8 mW
o
Terminal (21–22)
Input
U
, V
8.3 V
o
OC
I
, I
0.2 mA
o
SC
P
0.4 mW
o
Terminal (11, 12, 13, 14)
Input
U
, V
8.3 V
o
OC
I
, I
13.1 mA
o
SC
P
27.3 mW
o
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
U
m
Terminal (51, 52)
Supply
Voltage
Terminal (41, 42)
Output
Current
150
Group
C
o
IIC or A, B
80 nF
IIB or C, E, F
640 nF
IIA or D, G
2.1 µF
Group
C
o
IIC or A, B
80 nF
IIB or C, E, F
640 nF
IIA or D, G
2.1 µF
Group
C
o
IIC or A, B
7 µF
IIB or C, E, F
73 µF
IIA or D, G
1000 µF
Group
C
o
IIC or A, B
7 µF
IIB or C, E, F
73 µF
IIA or D, G
1000 µF
253 V, max. 400 Hz
19.2...31.2 V DC
0/4...20 mA
L
L
/R
o
o
o
4 mH
54 µH/Ω
16 mH
218 µH/Ω
32 mH
436 µH/Ω
L
L
/R
o
o
o
1000 mH
4 mH/Ω
1000 mH
17 mH/Ω
1000 mH
35 mH/Ω
L
L
/R
o
o
o
1000 mH
100 mH/Ω
1000 mH
400 mH/Ω
1000 mH
800 mH/Ω
L
L
/R
o
o
o
207 mH
1 mH/Ω
828 mH
5 mH/Ω
1000 mH
10 mH/Ω