Promass 64
Electrical data
PROMASS 64 with two phase-shifted pulse outputs, status output,
active current output, auxiliary input (Promass 64****-**********R)
Functional value
3
Ground connection (protective earth)
1
L1
for AC power supply
N
2
Voltage:
Power consumption:
20
Current output
21
22
Status output
23
Ground
24
Auxiliary input
25
26
Pulse output 1
27
Pulse output 2
28
Ground connection (signal cable shield)
PROMASS 64 with two phase-shifted pulse outputs EEx i, status output,
(Promass 64****-**********S)
Functional value
3
Ground connection (protective earth)
1
L1
for AC power supply
N
2
Voltage:
Power consumption:
22
Status output
23
Power
26
Pulse output 1
27
Pulse output 2
28
Ground connection (signal cable shield)
In the version with intrinsically safe outputs, an additional IP 40 cover is used for
the power supply terminals in the wiring compartment. Do not open the IP 40 cover
while circuits are alive! In the combination "EEx de wiring compartment" and
"intrinsically safe outputs", connection and disconnection of intrinsically safe wiring
(terminals 22/23 and 26/27), and measurements with certified measuring devices
is also permitted during operation.
Endress+Hauser
L+
for DC power supply
L–
AC 85...260 V
AC 20...55 V
DC 16...62 V
15 VA / 15 W
active, 0/4...20 mA
= 700 Ω
R
L
Relay
max. 30 V DC / 0.1 A
common ground for the status output
and the pulse outputs 1 / 2
3...30 V DC
Ri = 1.8 Ω
configurable, e.g. for resetting error
messages or positive zero return
f
= 500 Hz, active/passive
max
active: 24 V DC, 25 mA
passive: 30 V DC, 250 mA
90°/180° phase-shifted in relation to
pulse output 1
f
= 500 Hz, active/passive
max
active: 24 V DC, 25 mA
passive: 30 V DC, 250 mA
L+
for DC power supply
L–
AC 85...260 V
AC 20...55 V
DC 16...62 V
15 VA / 15 W
(open emitter)
max. 30 V DC, 25 mA
common power supply for the status
output and the pulse outputs 1 / 2
(open emitter)
f
= 500 Hz , passive
max
30 V DC, 25 mA
(open emitter)
90°/180° phase-shifted in relation to
pulse output 1
f
= 500 Hz, passive
max
30 V DC, 25 mA
Safety value
U
= 260 V
max
For connecting devices with U
= 260 V
max
and I
= 500 mA.
max
Safety value
U
= 260 V
max
Connection of a intrinsically safe current
circuit of the categorie "ia" or "ib":
Maximum value:
U
=
30 V
i
Internal capacitance
C
=
3 nF
i
Internal inductance
negligible
en
Power
L1/L+
supply cable
N/L-
Output
circuit cable
Power
L1/L+
supply cable
N/L-
Output
supply cable