14 EN – Quick installation and start-up guide
2
Run the motor cables to the enclosure. Ground the cable shields 360° at the enclosure entry.
3
Connect the twisted shields of the motor cables to the grounding terminal.
4
Screw in and tighten the insulators to the drive module by hand. Install the T3/W2 connection
terminal to the insulators.
5
Connect the phase T3/W2 conductors to the T3/W2 terminal.
6
Install the T2/V2 connection terminal to the insulators. See the warning in step 4.
7
Connect the phase T2/V2 conductors to the T2/V2 connection terminal.
8
Install the T1/U2 connection terminal to the insulators. See the warning in step 4.
EN
9
Connect the phase T1/U2 conductors to the T1/U2 terminal.
DA
10
Remove the plastic sheeting from the motor cable clear plastic shroud (option +B051) from
both sides.
DE
11
Install the shroud (option +B051) on the motor cable connections.
12
Install the lower front cover to the drive module.
ES
13
Drill holes for the power cables to the bottom clear plastic shrouds.
FI
14
Remove the plastic sheeting from the bottom clear plastic shrouds.
15
Install the bottom first shroud on the motor cable entry.
FR
16
Install the second shroud on the motor cable entry.
IT
Connect the input cables and install the shrouds (option
NL
+B051)
PL
See
Connecting the input power cables and installing the shrouds (page
PT
Step
Tasks (input cables)
SV
1
Ground the input cable shields (if present) 360° at the enclosure entry.
2
Connect the twisted shields of the input cables and separate ground cable (if present) to the
TR
enclosure grounding busbar.
3
Step drill carefully sufficiently big holes to the entry clear plastic shroud for the cables to be
ZH
connected. Align the holes in the vertical direction according to the alignment holes in the
shroud. Smooth the hole edges.
Remove the plastic sheeting from both sides of the shroud.
Attach the cables firmly to the enclosure frame to prevent chafing against the hole edges.
4
Put the conductors of the input cables through the drilled holes in the clear plastic shroud.
5
Connect the input cable conductors to the drive module L1/U1, L2/V1 and L3/W1 connection
busbars. For option +H370: Refer to the hardware manual.
6
Install the side clear plastic shroud and the upper front cover of the drive module.
7
Install the entry clear plastic shroud (option +B051) and motor cable shroud (option +B051).
8
Install the top clear plastic shroud (option +B051) to the drive module.
Connect the control cables to the integrated control unit
Connect the conductors of external control cables to the appropriate terminals of the
control unit. See section
Do not use longer screws or bigger tightening torque than given in the installation
drawing. They can damage the insulator and cause dangerous voltage to be
present at the module frame.
Default I/O connection diagram (page
302).