9
Technical specifications
RRS485 bus terminator: Switchable
EMC protection zone:
Load at 24 V output:
Rated discharge current:
24 V protection:
RS485 bus protection:
Closed-circuit current:
Permissible cable
cross sections:
Rigid cable:
Flexible cable with ferrule: 0.14 mm² to 1.5 mm²
Type of installation:
Housing dimensions:
(H x W x D)
32
1/2/3 (from main distributi-
on board)
Max. 5 A
10 kA @ 90 V
1 kA @ 38 V
1 mA @ 29 V
28 A @ 21 V
1 mA @ 15 V
10 mA
0.14 mm² to 2.50 mm²
TS 35 mounting rail as
per EN 50022 (standard
mounting rail, DIN rail)
Standard DIN rail housing
with width of 2 WM
87 x 36 x 65 mm