FUNCTION
MiniVent M1/100/120 F
3 .2

Accessories

WES 100
Wall mounting kit
Wall mounting kit
WES 120
Mounting flange
MF 100
Telescopic wall sleeve
TWH 100
Telescopic wall sleeve
TWH 120
Mounting plate
MBR
3 .3

Product service life

This unit is designed for a service life of at least 40,000 h, at S1 operation with maximum power in the maxi-
mum permissible ambient temperature.
3 .4

Dimensions

M1/100 F
Fig .1
All dimensions in mm
4 .0

Functional description M1/100/120 F

With integrated, electronic, humidity curve-dependent automatic control unit. If 70 % relative humidity (factory
setting), is exceeded or a rapid increase in humidity, the fan will be automatically activated. At the low stage as
standard. On the relative humidity falls below 60 % (factory setting), the fan will deactivate again. Regardless
of the humidity control system, the fan can be activated with an external switch (possibly connected to light)
with approx. 45 sec. start-up delay and approx. 6-minute overrun time (function input). Manual control (On/
Off) via a switch is also possible in parallel, which is secondary to the function input.
Configuration options / factory settings*:
− Start-up delay: 0 or 45 sec*.
− Overrun time: 6*, 12, 18, 24 min.
− A button (button impulse min. 0.5 sec.) can also be connected instead of the start-up delay, which activates
the fan for the set overrun time when pressed.
A button (button impulse min. 0.5 sec.) can also be connected instead of a start-up delay and overrun time
to temporarily (1 hr.) deactivate the automatic humidity system.
− Activation threshold humidity: 60/50 %, 70/60* %, 80/70 %, 90/80 %
− Automatic humidity control system: low stage*, high stage
Ref . no . 0717
Ref . no . 0486
Ref . no . 6188
Ref . no . 6352
Ref . no . 6353
Ref . no . 0281
M1/120 F
Fig .2
All dimensions in mm
4