Zulassungen, Normen und Richtlinien
Continuation
Required Markings
Internal Overload Protection Operates within 60 seconds when reaching 150 %
of the Motor Full Load Current.
Suitable for use on a circuit capable of delivering not more than 5 kA rms
symmetrical amperes, 230 Volts for INV Mx 2 or 480 Volts for INV Mx 4,
maximum when protected by fuses.
"Warning" – Use fuses rated 600 V/50 A for INV MA 2 only.
"Warning" – Use fuses rated 600 V/10 A for INV MA 4 only.
"Warning" – Use fuses rated 600 V/30 A for INV MB 4 only.
"Warning" – Use fuses rated 600 V/30 A for INV MC 4 only.
"Warning" – Use fuses rated 600 V/70 A for INV MD 4 only.
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
Manufacturer Instructions, National Electrical Code and any additional local
codes.
All wiring terminals marked to indicate proper connections for the power
supply, load and control circuitry.
Instruction for operator and servicing instructions on how to mount and
connect the products using the intended motor connection adapter,
please see chapter 3.3 and 9.1 in the operating manual.
Use 75° C copper wires only.
Drives do not provide over temperature sensing.
For use in Pollution degree 2 only.
For Mx 4 used in Canada: TRANSIENT SURGE SUPPRESSION SHALL BE
INSTALLED ON THE LINE SIDE OF THIS EQUIPMENT AND SHALL BE RATED
277 V (PHASE TO GROUND), 480 V (PHASE TO PHASE), SUITABLE FOR
OVERVOLTAGE CATEGORY III, AND SHALL PROVIDE PROTECTION FOR A
RATED IMPULSE WITHSTAND VOLTAGE PEAK OF 2.5 kV