Herunterladen Inhalt Inhalt Diese Seite drucken

Comprag DV75 Bedienungsanleitung Seite 23

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

SEQ PARAM SET
GRP MST/FOLLOWER
GRP MODE
V-V/V-F
GRP NUMBER 0002
GRP SWITCH
0099H
GRP LD
05.2 BAR Group load pressure.
GRP ULD
08.0 BAR Group idle run pressure.
GRP DELAY
0020s
RST MAINT TIME
OIL FILTER
0000H
SEPARATOR
0000H
AIR FILTER
0000H
OIL
0000H
GREASE M1
0000H
BELTS
0000H
MAX RUN TIME
OIL FILTER
0500H
SEPARATOR
4000H
AIR FILTER
2000H
OIL
0500H
GREASE M1
4000H
BELTS
4000H
USER PASS
ENTER PASSWORD
LANG.
LANGUAGE
If there is no activity for 60 seconds in the current menu, the control will automatically return to the main menu.
COMPRAG
Screw air compressor DV-Series
— group parameters
Options: master / follower (slave).
Options: individual operation / group.
Number of the compressor within the group.
Group delay, wait time until next compressor switches.
— resetting of the maintenance hours counter
Oil filter maintenance. Set to 0 after maintenance.
Separator maintenance. Set to 0 after maintenance.
Air filter maintenance. Set to 0 after maintenance.
Oil. Set to 0 after changing.
Lubricate motor bearings. Set to 0 after maintenance.
Change belts. Set to 0 after maintenance.
— set maintenance intervals.
Oil filter maintenance. Set maintenance interval.
Separator maintenance. Set maintenance interval.
Air filter maintenance. Set maintenance interval.
Oil. Set change interval.
Lubricate motor bearings. Set maintenance interval.
Change belts. Set to 0 after maintenance.
— user password
****
No access to parameter
— language
........ EN/DE
23