Installation and Operating Instructions
m
DANGER
* (performance and noise data from the
currently valid Helios publications and the
internet)
Axial high-performance fans EC – HQ EC / HW EC / HRF EC
In case of a storage period of more than three months or motor standstill, maintenance must be carried out before
commissioning according to chapter 4. In case of reshipment (above all over longer distances; e.g. by sea), it must be
checked whether the packaging is suitable for the form and route of transport. Damages due to improper transportation,
storage or putting into operation are not liable for warranty.
1�9 Standard version
These installation and operating instructions describe the EC axial high-performance fan series:
Series
EC axial high-performance fans HQ EC
EC axial high-performance fans HRF EC
EC axial high-performance fans HW EC
Binding information on the individual EC fan types can be found on the type plates.
1�10 Area of application
– Intended use: The EC axial high-performance fans are suitable for conveying normal or slightly dusty (particle size < 10 μm),
less aggressive and humid air, in moderate climates and in the range of their performance curves, see Helios sales documents
/ internet. The permissible medium and ambient temperature is -30 °C to +40 °C. If applicable, deviating temperatures can
be found on the type plate. The EC axial high-performance fans are designed as components of a stationary ventilation unit
for buildings. They can only be operated once they have been installed for their intended purpose and safety is ensured by
safety devices.
The motor is approved for relative humidity of 100% in a continental climate without any further environmental influences.
In the case of longer downtimes in a humid atmosphere, it is recommended to run the motor / fan for at least two hours a
month at 80-100 % of the maximum speed so that any moisture that may have penetrated can evaporate.
– Reasonably foreseeable misuse: The EC fans are not suitable for operation under difficult conditions, such as high levels
of humidity, aggressive media, long standstill periods, heavy contamination, excessive loads due to climatic, technical or
electronic influences. The same applies for the mobile use of EC fans (vehicles, aircraft, ships, etc.). Usage under these
conditions is only possible with release approval from Helios, as the standard version is not suitable in this case.
– Improper, prohibited use: Any use other than the intended use is not permitted! The conveying of solid matter or solid
matter content > 10μm in air and liquid is not permitted. The EC fans must not be operated in contact with water and
effective weather protection must be ensured in case of outdoor installation. Transport media, which affect the materials of
the EC fan, and abrasive media are not permitted. The EC fan may only be operated in the specified performance curve
range. Usage outside of the performance curve range is not permitted and can lead to the excessive heating of the motor,
and strong vibrations and increased noise generation may also occur.
m Use in explosive atmospheres is not permitted!
1�11 Performance data
The unit type plate gives an indication of the mandatory electrical values; which must be coordinated with the local sup-
ply network. The fan performances* were established on a test stand according to DIN EN ISO 5801; they apply to the
nominal speed and standard design using an inlet nozzle, without a protection guard and with unhindered inflow and
outflow. Different versions and unfavourable installation and operating conditions can lead to a reduction of output.
1�12 Noise data
The noise data* also refers to the aforementioned directive. Housing variations, unfavourable operating conditions and
many other things can lead to an increase in the specified catalogue values. Data that refers to certain distances (1, 2,
4 m) apply to free field conditions. With regard to installation, the sound pressure level can differ significantly from the
catalogue data, as it is highly dependent on the installation conditions, i.e. on the absorption capability of the room, the
room size among other factors.
1�13 Type plate / Technical data
The product-specific technical data can be found on the type plate. The individual data is described
below using an example.
.
HELIOS VENTILATOREN
78056 Villingen-Schwenningen Germany
Type: HQW EC 315 A
208 - 277 V
1~
u
2040 U/min
Cos ö 0,57
s
IP 44
TN 40°C
h
ç = 32,5 %
(A, statisch)
k
Signal code Type plate EC fan:
q Manufacturer's address
w Version:
HQW EC = Type designation
W = Single phase or D = Three phase
315 = Size
A = Type A or B = Type B
e Ref no.
r Serial number
t EC fan label:
EC version
EC version
EC version
q
Art-Nr. 4880/001
PC 54012
e
w
Ser.Nr.
123456/
011
1,5 A
0,19 kW
i
o
50/60 Hz
Th.-Cl. 155
d
f
j
N= 43,8
VSD integrated
l
;
o Nominal current [A]
a Nominal power absorbed [kW]
s Nominal speed [U/min]
d Cosine in rated operation
f Frequency [Hz]
g Motor insulation class
h IP = Protection class
j Maximum ambient air, air flow temperature
k Efficiency factor in BEP
3
Diameter
Ø 250-500 mm
Ø 250-710 mm
Ø 250-500 mm