INSTALLATION EXAMPLES

HL_PC / HL_PCM
wall-mounted
installation
HL_PC / HL_PCM
wall-mounted
installation,
without skirting
with feet
(ZH1 / ZH1B)
COIL ROTATION
If the hydraulic connections require the
rotation of the coil, remove the cabinet
and ambient probe then proceed as
follows:
– remove the electrical connections from
the terminal strip;
– remove the probe from the coil;
– remove the screws fixing the basin and
remove it;
– remove the screws securing the coil,
then remove the coil;
– remove the push-outs on the righthand
side;
– rotate the coil and secure it with the
INSTALLING THE ELECTROSTATICALLY PRECHARGED AIR FILTER
Installation
- Remove the ventilation grille from the
unit. Use the point of a tool to place pres-
sure on the upper hooks of the grille.
- Remove the filter from its sealed pack-
age.
- Insert the filter in the suction grille.
- Reattach the ventilation grille to the
unit. First insert the lower hooks of the
cover, and then insert the upper hooks.
Characteristics
Class 2 (UL 900).
Easy to remove, it is supplied in a
previously removed screws;
– reassemble the tray, fixing it with the
screws. All the trays are suitable for
condensate drainage on both sides;
N . B . : B e f o r e c o n n e c t i n g t h e
condensate discharge, use a tool to
knock out the diaphragm of the tray
on the water connections side.
– position the polyethylene cap of
the condensate discharge onto the
lefthand side;
– remove the electric motor cable from
the right-hand side;
– remove the rectangular push-out from
sealed box only to be opened when
it is to be used.
The electrostatic precharge of the filter
is spent after two years of the box
being opened, after this period it
behaves like a normal filter.
For this reason replacement over two
years with a new one is recommended
(available as a spare part from Aermec
After Sales centres).
Maintenance
HL_PC / HL_PCM
ceiling installation
HL_PC / HL_PCM
wall-mounted
installation with
skirting and feet
(ZH1M / ZH1MB)
the left-hand side;
– recover the cable grommet and insert it
in the left-hand side before closing the
right-hand hole with adhesive tape;
– move the electric motor cable onto the
left-hand side, passing it through the
cable grommet and arranging it so it
reaches the connector on the side;
– unravel the twists and turns of the
microswitch cable for the length
necessary to reach the control board on
the left-hand side;
– fasten the microswitch cable to the
cable clamps.
Cleaning frequently, removing
the dust that has built up using a
vacuum, the use of water and cleaning
substances considerably speeds up the
electrostatic precharge deterioration.
IHLPCLJ 2204 - 6887206_05