Service
Code
Description
955
Water flow check error
970
Aux. pump configuration mismatch
2P2
Thermal cleanse not complete
2P3
DHW setpoint not reached in boost
2P4
Electr. heater thermos. (manual)
2P5
Electr. heater thermostat (auto)
2P7
Precirculation error
2P8
Low pressure warning
2P9
SG ready input config. err.
72 / EN
Check the connection of the flow and return temperature sensors
Check the configuration of parameter 1.2.5
Sanitisation temperature not reached in 6 h:
Check the drawing of domestic hot water during the thermal sanitisation
Check the activation of the heating element
Domestic hot water set-point temperature not reached during the boost
Check the drawing of domestic hot water during the DHW boost cycle
Check the activation of the heating element
Check the activation of the main circulation pump
Check the flow with the reading of the flow meter through parameter
Check the condition of the safety thermostat and of the cabling
Check the activation of the main circulation pump
Check the flow with the reading of the flow meter through parameter
Check the condition of the safety thermostat and of the cabling
Check the connection of the flow meter
Run an automatic deaeration cycle 1.12.0
Check for any water leakages in the hydraulic circuit
Faulty pressure switch
Defective cabling of the pressure switch. Check the connection of the pres-
sure switch and replace it, if necessary.
Only one of the parameters 1.1.0 or 1.1.1 is set as an SG Ready input