Connection of the bus line
•
Connection takes place using the 9-pole DSUB socket on the UMG96S.
•
Use the plug supplied.
•
Connect the incoming „M+" line to terminal 4 in the plug and
„M-" to terminal 2.
•
Connect „M+" to terminal 9 and „M-" to terminal 7 for any contin-
uing bus line.
•
Make sure that terminals 4/2 and 9/7 in the UMG96S are bridged.
•
The load of the M-Bus of one UMG96S is 1.5mA of the load of one
M-Bus device.
Illustration 2. Connection using the M-Bus plug provided in the delivery.
22
M-Bus connector
D-Sub,
D-Sub,
9-pin,
Item-Nr. 13.10.514
9-pin,
plug socket
connector
Screw
terminal