Setting the parameters
The parameters for the primary address, the baud rate and the number
of data points are set-adjusted directly on the UMG96S. A description for
the programming of parameters can be found in the operating instruc-
tions for the UMG96S in Chapter „Parameters and measured values".
M-Bus Address
The M-Bus address consists of the primary address at least. In addition,
the UMG96S can be accessed over the secondary address.
Primary address
The M-Bus subscriber can be addressed over the primary address. You
can employ the primary addresses from 1 to 250 for the UMG96S. The
addresses 0, 251 to 255 are reserved for special tasks. The primary
address can be changed over the M-Bus.
Secondary address
The secondary address consists of the extended secondary address
and a device-specific part.
•
The device-specific secondary address part cannot be changed.
•
The secondary address consists of 8 bytes and is BCD coded.
•
The extended secondary address is preset with the device serial
number.
•
The extended secondary address can be changed by the customer.