Number of data points

Here you stipulate how many data points should be transmitted. Individual
data points cannot be selected.
Example: Reading out the data points 1 to 6.
Enter a 6 into the UMG96S on address 82.
All data points, up to and including data point 6, are transmitted with
every request.
Example: You require only the data point 10.
Enter a 10 into the UMG96S on address 82.
All data points, up to and including data point 10, are transmitted with
every request.
Use only the data point 10 required and ignore the received but not
required data points.
Address Meaning
080
M-Bus primary address (UMG96S)
081
M-Bus baud rate
082
Number of data points for RSP_UD2
083
As an extension secondary addr., Part 1 0 .. 99
084
As an extension secondary addr., Part 2 0 .. 99
085
As an extension secondary addr., Part 3 0 .. 99
086
As an extension secondary addr., Part 4 0 .. 99
1)
0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200, 7 = 38400
baud
2)
0 = All data points. In order to call up all data points, one telegram must be sent.
The extended secondary address is preset by the manufacturer with the device
3)
serial number.
UMG 96S / English
Setting range Pre-setting
0 .. 250
1
0 .. 7
5
1)
0 .. 27
0
2)
3)
3)
3)
3)
25