EGEA
200 LT - 260 LT - 200 LT-S - 260 LT-S
Damper "A"
open
fig. 15- Example of installation in the winter period

6.4 Securing and connections of this appliance

The product must be installed on a stable, flat floor that is not
subject to vibrations.

6.5 Aeraulic connections prohibited

Water heater that draws the air from a heated room.
• Connection to the VMC.
• Connection on the attic.
• Connection to the external air in the intake and expulsion of
the fresh air inside.
• Connection to a Canadian well.
• Water heater installed in a room containing a natural draft
boiler and channeled to the outside for the release of air only
• Aeraulic connection of the appliance to a tumble dryer.
• Installation in dusty rooms.
• Withdrawal of air containing solvents or explosive materials.
• Connection to hoods that evacuate greasy or polluted air.
• Installation in a freezing room.
• Objects placed above the water heater.
Mandatory air
inlet D.160 mm
Damper "B"
closed
Internal
compartment
cod. 3541T600 - Rev. 08 - 12/2021

6.6 Hydraulic connections

Connect the cold water supply line and the outlet line to the ap-
propriate connection points (fig. 16).
The table below gives the characteristics of the connection
points.
Ref.
Function
1
Cold water inlet
2 *
Solar coil outlet
3 *
Solar coil inlet
4
Recirculation
5
Hot water outlet
6
Condensate drain
Pit for solar probe and ther-
A *
mal cut-out bulb
*: only for 200 LT-S and 260 LT-S models.
6
B
4
3
2
Model 200 l / 260 l
1"G
3/4"G
3/4"G
3/4"G
1"G
1/2"G
1/2"G
5
A
1
fig. 16
EN
107