Herunterladen Inhalt Inhalt Diese Seite drucken

Installation And Commissioning; Storage; Limits Of Use; Operating Limits - Ferroli EGEA 90 LT Handbuch Für Betrieb Und Installation

Vorschau ausblenden Andere Handbücher für EGEA 90 LT:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 254
EGEA
90 LT - 120 LT
6.
INSTALLATION AND
COMMISSIONING
Product installation, commissioning and maintenance
must be carried out by qualified and authorised per-
sonnel.
Any intervention on the de-
vice, including disposal, must
be performed by qualified per-
sonnel with a suitable Refrig-
eration Technician's Licence
aimed at the knowledge and
EXPERT
R290
TECHNI-
management of systems con-
CIAN
taining HC type gases such as
R290 (Propane).
Comply with the warnings given in chapter 8 on page 148.
6.1

STORAGE

For
the
equipped with flammable refrig-
erant gas, refer to local regula-
R290
tions in force.
NEVER place the device outdoors; atmospheric agents
would damage it, making it unreliable and dangerous for
the operator and user.
6.1.1 Environmental storage conditions
The device must be stored in a dry place, protected from dust
or anything else that may damage it.
Ambient temperature (min. / max.)
-20 °C / +70 °C
6.2

LIMITS OF USE

This product has not been de-
signed, nor is it intended as such,
to be used in hazardous envi-
ATTENTION
ronments according to Directive
2014/34/EU (due to the presence
of potentially explosive atmos-
pheres - ATEX).
PROHIBITION
storage
of
devices
cod. 3541T580 - Rev. 07 - 12/2022
Or for applications that require a
degree higher than IP24 or that
require safety features (fault-tol-
ATTENTION
erant, fail-safe) such as life sup-
port systems and/or technolo-
gies or any other context in which
the malfunction of an application
PROHIBITION
may lead to the death or injury of
persons or animals, or to serious
damage to property or the envi-
ronment.
If a fault or malfunction of the
product could cause damage
(to persons, animals and prop-
erty), then a separate, perfor-
mance-monitoring system is re-
quired, equipped with alarms to
exclude such damage.
6.3

OPERATING LIMITS

The product in question is designed exclusively for heating hot
water for sanitary uses within the limits described below.
For this purpose, it must be connected to the domestic water
supply and the power supply (see chapter "6. INSTALLATION
AND COMMISSIONING").

6.3.1 Temperature range

80
75
70
65
60
B
55
50
45
40
35
0
10
-5°C
fig. 28 - Chart
A = Inlet air temperature (°C)
B = Hot water temperature (°C)
= Operating range for heat pump (HP)
= Integration with heating element only
75°C
62°C
38°C
20
30
40
50
A
43°C
EN
133

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

Egea 120 lt

Inhaltsverzeichnis