The free lateral connection of the red measurement valve is provided for
connecting a pressure measuring instrument to test the system. Test
reports can be found at www.afriso.de.
1. Connect the pressure measuring instrument (vac-
2. Set the measurement valve (red connection) to
3. Set the test valve (white connection) to position
4. Observe the pressure measuring instrument and
5. Set the test valve (white connection) to position
6. Compare the recorded values to the set values.
7. Set the measurement valve (red connection) to
8. Remove the pressure measuring instrument.
1. Press the Test key.
- The green LED, the red LED and the yellow LED light up and the
audible alarm sounds.
- The function test is terminated once you release the Test key.
uum).
position "Test".
- The pressure measuring instrument indicates the
vacuum in the interstitial space.
"Vent".
- The vacuum drops slowly.
document the pressure values at which the pump and
the alarm signals are switched on.
"Normal Operation".
position "Normal Operation".