Verify that the pressure in the interstitial space of the tank corresponds to the
specifications.
Verify that the product has been properly mounted and electrically
connected.
Verify that both valves are in the position "Normal Operation".
Verify that the interstitial space has been evacuated with a vacuum of
approximately 370 mbar.
Verify that the tightness test of the interstitial space has been properly
performed.
Verify that the suction line and the measuring line are connected to the
interstitial space.
1. Apply voltage via the on-site mains fuse.
- The green LED is on.
- Once the correct vacuum is reached, the pump switches off.
- The system is now ready for operation.
2. Perform a function test.
The specialised company certifies the installation, commissioning and test of
the product (see chapter "Certificate of expert").
Eurovac HV
EN