Technical Data

Device supply
Rated control circuit supply voltage U
Control supply voltage range
Rated control supply current I
Protective circuits
Digital input in acc. IEC 60947-1 Annex S
Rated actuating voltage U
Rated actuating current I
Switching level
Switch-On time typ.
Switch-Off time typ.
Maximum switching frequency
AC output
Rated operational voltage range U
Rated insulation voltage U
Load current range, see 18 Derating
Maximum starting current
Rated conditional short-circuit current I
SCCR
Trigger characteristic
Tripping current
Overload cooling time
100% to 75% (Resistive, nominal current 1 A)
100% to 75% (Resistive, nominal current 3 A)
Thermal capacity at operation with nominal
current
Rated operating current I
Rated operating current Ie AC-51
Leakage current
Protective circuits
Indication of main button LEDs
Ready for Operation
Operation Mode (Forward / Backward)
Warning
Error
Page 68 of 71
S
S
C
C
e
i
q
AC-53a
e
94 641 000 B
24 V DC
20,4 V DC - 26,4 V DC
200 mA
Overvoltage protection
Reverse polarity protection
24 V DC
7 mA
< 6 V („0"/Low-Signal)
>12 V („1"/High-Signal)
< 20 ms
< 20 ms
20 Hz
130 V AC - 500 V AC
500 V AC
0,1 - 2,6 A / 0,1 A - 6,6 A
35A (2,6 A) / 56A (6,6 A)
100 kA (coordination type 2,
without additional fuse)
100 kA
Resistive
110% Nominal current
Dynamic, see cool down time
(chapter 16)
3.46 s
3.46 s
75%
2,6 A / 6,6 A
2,6 A / 6,6 A
0,5 mA
Overvoltage protection
Varistors
white
green
yellow
red
Revision 09.2022