7.3 Standard connection

The standard connection is made using a 16-pin connector. Connect the cables to the
control plug of the electronic switch.
To put the load into operation, you have to enable the device via the enable input by
supplying 24V between EN+ and EN-.
As soon as a valid signal is present at the enable input (at terminals EN + and EN-), the
device will accept control commands.
It is possible to assign a persistent valid signal at the enable inputs through connecting
terminals (6) and (5) as well as terminals (8) and (7).

7.3.1 3-Phase Configuration

Pin assignment – Control Plug, 3~-Configuration
Figure 7
The control inputs Control Load and Reset are galvanically isolated from the 24V control
circuit.
Common reference for those control inputs is terminal GND for inputs.
The enable terminals Enable + and Enable - are galvanically isolated from the 24V control
circuit and from the other control inputs.
Since a base insulation exists, it is allowed to wire the terminals GND for inputs and GND
together.
WARNING:
Do not use control voltages > 24V.
!
Control voltages >24V will damage the device.
Page 47 of 71
2
Control Load
4
Not connected
6
24 V / L+
8
GND / L-
10 Reset
12 GND for inputs
14 98 (Error NO)
16 12 (Warning NC)
94 641 000 B
English.
1
24 V / L+
3
GND / L-
5
Enable +
7
Enable -
9
Not connected
11 C/Q (IO-Link)
13 96 (Error NC)
15 95/11 (Common)
Revision 09.2022