OMUS®C14 Operating Instructions
7.3 Standard connection
•
The standard connection is made using a 16-pin connector. Connect the cables to the
control plug of the electronic switch.
•
To put the load into operation, you have to enable the device via the enable input by
supplying 24V between EN+ and EN-.
•
As soon as a valid signal is present at the enable input (at terminals EN + and EN-), the
device will accept control commands.
•
It is possible to assign a persistent valid signal at the enable inputs through connecting
terminals (6) and (5) as well as terminals (8) and (7).
7.3.1 3-Phase Configuration
Pin assignment – Control Plug, 3~-Configuration
Figure 7
•
The control inputs Control Load and Reset are galvanically isolated from the 24V control
circuit.
•
Common reference for those control inputs is terminal GND for inputs.
•
The enable terminals Enable + and Enable - are galvanically isolated from the 24V control
circuit and from the other control inputs.
•
Since a base insulation exists, it is allowed to wire the terminals GND for inputs and GND
together.
WARNING:
Do not use control voltages > 24V.
!
Control voltages >24V will damage the device.
Page 47 of 71
2
Control Load
4
Not connected
6
24 V / L+
8
GND / L-
10 Reset
12 GND for inputs
14 98 (Error NO)
16 12 (Warning NC)
94 641 000 B
English.
1
24 V / L+
3
GND / L-
5
Enable +
7
Enable -
9
Not connected
11 C/Q (IO-Link)
13 96 (Error NC)
15 95/11 (Common)
Revision 09.2022