OMUS®C14 Operating Instructions
Connections
WARNING: Danger to life by electric shock!
!
Never carry out work when voltage is present.
7.1 Main connection and line protection
•
When making the mandatory 3-phase connection, it is essential to observe the terminal
identification for correct phase sequence.
•
The control supply voltage and control voltage inputs must be operated with power supply
modules according to IEC 61131-2 (max. 5 % residual ripple).
•
In order to avoid inductive or capacitive coupling of noise emissions on long control wires,
the use of shielded conductors is recommended.
•
7.2 Mounting
•
Snap the electronic switch onto the respective busbar system 30Compact, 60Classic or
directly onto the CrossBoard®.