OMUS®C14 Operating Instructions

5.3 UL notes

WARNING: Risk of electrical shock and fire!
!
The opening of the branch-circuit protective device may be an indication that a fault current
has occurred.
To reduce the risk of fire or electric shock, current-carrying parts and the other components of
the controller should be examined and replaced if damaged.
Failure to follow instructions can result in death, serious injury, or equipment damage.
NOTE: The device is designed for use with a "low voltage, limited energy, isolated
!
power supply". Use copper cables approved to at least 75 °C.
SCCR
Suitable for use on a circuit with a maximum of 100 kA rms symmetrical amperes and ≤480 V.
FLA 2,6 A (480 V AC), 6,6 A (480 V AC).