OMUS®C14 Operating Instructions
19.4.5 Single-Phase Operation – Configuration L2
ISDU-
Index
Name
258
Nominal current
261
Trip class
265
Undercurrent detection
– Enable
269
Undercurrent detection
– Threshold
273
Undercurrent detection
– Fault Type
277
Undervoltage detection
– Enable
281
Undervoltage detection
– Threshold
285
Undervoltage detection
– Fault Type
Overvoltage detection –
289
Enable
Overvoltage detection –
293
Threshold
Overvoltage detection –
297
Fault Type
Page 66 of 71
Data-
Length
type
(Bytes)
uint8
1
uint8
1
uint8
1
uint8
1
uint8
1
uint8
1
uint16
2
uint8
1
uint8
1
uint16
2
uint8
1
94 641 000 B
Description
Unit in 100mA
Maximum value:
26: 2,6A device
66: 6,6A device
8: Resistive
0: Disabled
1: Enabled
Unit in 100mA
Maximum value:
Actual set nominal
current
0: Warning
1: Error
0: Disabled
1: Enabled
Unit in 10mV
Maximum value:
600V
0: Warning
1: Error
0: Disabled
1: Enabled
Unit in 10mV
Maximum value:
600V
0: Warning
1: Error
Revision 09.2022
Access
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write
Read
Write