Tripping curve (cold state)

The tripping characteristic represent an overview of the times after which the OMUS®C14
switches off due to an overload that has occurred. In the cold state, a start value equal to 0 is
assumed for the thermal capacity.
12
10
8
6
4
2
0
1
3
Figure 17
Tripping time (cold state)
Table 1: Tripping time [s] (cold state)
Page 56 of 71
5
7
9
Overcurrent factor I/I
I / I
N
RESISTIVE
1,2
1,5
2
3
4
5
6
7
8
9
10
11
12
13
14
15
94 641 000 B
11
13
N
TC
10
3.56
1.62
0.66
0.38
0.24
0.18
0.14
0.12
0.1
0.08
0.08
0.06
0.06
0.06
0.06