Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 181

Operating area

For proper functioning and a good temperature distribution,
the stove shoul be positioned in a location where it is able to
take in the air necessary for combustion of the pellet (about
40 m
/h must be available, as laid down in the standard
3
governing the installation and in accordance with local
national standards).
The volume of the room must not be less than 30 m
The air must come in through permanent openings made in
walls (in proximity to the stove) which give onto the outside,
with a minimum cross-section area of 100 cm
These openings must be made in such a way that it is not
possible for then to be obstructed in any way. Alternatively,
the air can be taken from rooms adjacent to the one which
needs ventilating, as long as they are provided with an air
intake from the outside, and are not used as bedrooms or
bathrooms, and provided there is no fire risk such as there
is for example in garages, woodsheds, and storerooms, with
particular reference to what is laid down in current standards.
It is not permissible to install the stove
in bedrooms, bathrooms, or in a room
where another heating appliance is
installed (fireplace, stove etc.) which does not
have its own independent air intake.
Locating the stove in a room with an explosive
atmosphere is prohibited.
The floor of the room where the stove is to
be installed must be strong enough to take
its weight. If walls are flammable, maintain a
minimum distance of 20 cm at the rear (A), of 40
cm at the side (B) and 100 cm at the front. If the
room contains objects which are believed to be
particularly delicate, such as drapes, sofas and
other furniture, their distance from the stove
should be considerably increased.
If the stove is installed on a flammable
floor it must be interposed with a slab of
insulating material to heat it protrudes
at least 20 cm on the sides and 40 cm
on the front.
In the presence of wood floors, install a
floor protection surface in compliance
with the rules in force in the country
.
3
.
2
Connection to the external air intake
It is essential that at least as much air must be able to flow
into the room where the stove is installed as is required for
proper combustion in the appliance and for the ventilation
of the room. This can be effected by means of permanent
openings in the walls of the room to be ventilated, which give
onto the outside, or by single or collective ventilation ducts.
For this purpose, on the external wall near the stove, a hole
must be made with a minimum free cross-section of 100 cm
(equivalent to a round hole of 10 cm diameter or a square
hole 10x10 cm) protected by a grille on the inside and the
outside.
The air intake must also:
• communicate directly with the room where the stove is
installed
• be protected by a grille, metal mesh or suitable guard, as
long as this does not reduce the area below the minimum.
• positioned in such a way as to be impossible to obstruct.
Min.
100 cm
2
.
2
page 5 of 36

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Mia 16Denia 14cMia 16c1212c

Inhaltsverzeichnis