Alarm text
A1
Pressure sensor mal-
function
A2
Temperature sensor
malfunction
A3
Flow sensor
malfunction
A5
Tundish sensor
malfunction
A6
Pressure too low
A7
Change of batteries
A8
Stagnation flush time
exceeded
A9
Flush time interval
exceeded
A20
No. of flushes excee-
ded
Assembly, commissioning, operation and maintenance HygBox Connect
Cause
The pressure sensor does not report
anything. There may be a defect.
The temperature sensor does not
report anything. There may be a defect.
No turbine pulses were recorded over
an extended period of time. The turbine
or the sensor may be dirty or faulty.
Flushing was interrupted because the
tundish sensor detected an overflow.
Flushing has not been started because
the required operating pressure is too
low.
Batteries are spent
The flush time of the stagnation
flushing has been exceeded.
The flush time of the interval flushing
has been exceeded
The maximum number of temperature
flushings within 24 hours has been ex-
ceeded.
Remedy
Please contact the SYR service.
Please contact the SYR service.
Open a water tapping point
and check whether turbine pul-
ses are displayed on the LED.
Please contact the SYR service.
Make sure that the tundish is
free.
Please check the installation.
Flushing will be resumed when
the operating pressure is rea-
ched.
Please replace the batteries.
Open a water tapping point
and check whether turbine pul-
ses are displayed on the LED.
Please contact the SYR service.
Open a water tapping point
and check whether turbine pul-
ses are displayed on the LED.
Please contact the SYR service.
Increase the number of flus-
hings or check the installation.