3.6_ OPTIONAL ACCESSORIES
The range of TSKY-B motors can be completed with the following optional accessories:
• 100BANT (fig. 33) Adaptor for up-and-over doors.
100BANT must be used to power operate counterweight up-and-over doors with
drive models TSKY-B and TSKY1-B.
• P-150SETSKY external manual release for application on handle (see relative instructions). • 100PROB (fig. 16 - 25) Extension for TSKY-B with belt.
• 750BATTSKY: Battery pack (see relative instructions).
3.7_ ELECTRICAL CONNECTIONS
All electrical connections must be made withthe system disconnected from the power supply.
1_
To open the protection cover and access the electronic control unit of TSKY-B, press on the side of the cover and turn the panel door as
shown in fig. 34.
2_
Route the connection cables to the various devices through the cable clamps, leaving a length 20÷30cm more than necessary. See para. 2.2
for the type of cables and figure 3 for connections.
3_
Make the connections as shown in the diagram in figure 35. Terminals are removable to facilitate connections.
3.8_ CONNECTING TO THE POWER SUPPLY
For electric power supply of TSKY-B simply connect the 230 Vac line to the transformer safety fuse holder (A fig. 35).
TSKY-B must be connected to the power mains by skilled and qualified personnel, in possession of all requirements for full com-
pliance with all legal provisions, standards and regulations.
The electric power line must be protectedagainst short circuits and dispersion to earth; a device must be fitted to enable shutoff
of the power supply during installation or maintenance of TSKY-B.
4. MANUAL RELEASE
If manual movement of the door is necessary, due to a power failure or problem with the automation, the release device is used as follows:
1_ In the case of the traditional release system, pull the knob downwards as shown in fig. 31.
2_ In the case of external release (8 fig. 3), turn the handle.
3_ Manually open or close the door.
5.RESTORING NORMAL OPERATION
To restore normal automation operation, return the door to the initial position when you hear the carriage re-engage.
Caution: if you do not hear the carriage re-engage (when the initial position is with the door closed), activate the operator (via radio
control, key-operated selector switch etc.); a number of complete manoeuvres are required to repeat automatic self-learning of the
travel limits.
6.FINAL CHECKS AND START-UP
I
mmediately after powering up TSKY-B, perform a number of simple checks:
- Ensure that the motor does not activate any door movement and that the courtesy light is off.
If this is not so, disconnect the control unit from the power supply immediately and check the electrical connections carefully.
Other useful information for troubleshooting can be found in chapter 12 "Troubleshooting".

7.TESTING AND COMMISSIONING

This is the most important phase of automation set-up to ensure maximum system safety.
The test can also be performed as a periodic check of automation devices.
Testing of the entire system must be performed by skilled and qualified personnel, who are responsible for the tests required
to verify the solutions adopted according to the risks present, and for ensuring observance of all legal provisions, standards
and regulations, with particular reference to all requirements of the standard EN12445 which establishes the test methods for
testing automations for power-operated gates and doors.
7.1. TESTING
Each automation component, such as sensitive edges, photocells, emergency stop, etc., requires a specific testing phase; for these devices take
care to follow the procedures specified in the respective instruction manual.
To test TSKY-B, perform the following sequence of operations:
1_
Ensure that all contents of chapter 1 "WARNINGS" are strictly observed.
2_
Release the door by pulling the release cord downwards. Check that it is possible to move the door in the opening and closing directions
with a maximum force of 225N.
3_
Re-engage the carriage.
4_
Using the selector or radio transmitter, test door closing and opening and ensure that movement is as envisaged.
5_
A number of tests are recommended to assess smoothness of door movement and check for any assembly or adjustment defects, as well
as for any points of friction.
6_
Check operation of all system safety devices one at a time (photocells, sensitive edges etc.);
7_
To test photocells and in particular that there is no interference with other devices, pass a cylinder (diameter 5cm, length 30cm) through the
optic axis joining the pair of photocells, first close to the TX and then the RX and then mid-way between the two. Ensure that in all cases the
device engages, changing from the active status to alarm status and vice versa, and finally that the action envisaged occurs on the control
unit, for example that during the Closing manoeuvre, the door inverts the current movement.
8_
If hazardous situations generated by the moving door are protected by means of impact force limitation, measure the force as specified in
the standard EN 12445. If the settings "speed" and "gearmotor force" control are used as an auxiliary function with the system for reduction
• 100BINSUPP (fig. 3): Additional Ceiling Fixing Kit.
• 100PROC (fig. 8 - 13): Extension for TSKY-B with chain.