PROGRAMMING THE OPERATIONAL LOGIC
It is possible for the control unit to use several different operational logic states, by simply moving the dip-switches located on the card.
The functions associated with each individual dip-switch are listed below.
DIP
FUNCTION
1
Pre-flashing
2
Automatic closure
Start during
3
opening
4
Operational logic
5
Slow down
6
Start off
7
Anti-slip
8
Photocell
9
Photocell test
10
Safety edge type
11
Safety edge
12
Safety edge test
SETTING
ON
Disabled
OFF
Enabled
ON
Enabled
OFF
Disabled
ON
Not accepted
OFF
Accepted
ON
Inversion
OFF
Step
ON
Enabled
OFF
Disabled
ON
Disabled
OFF
Enabled
ON
Disabled
OFF
Enabled
ON
Always active
OFF
NOT active during
opening
ON
Enabled
OFF
Disabled
ON
Conductive rubber
edge
OFF
Standard or optical
edge
ON
Always active
OFF
NOT active during
opening
ON
Enabled
OFF
Disabled
DESCRIPTION
The blinker is switched on when the motors are started
The blinker is switched on for 2 seconds before the motors are started
The gate is closed automatically after the period of time set by the PAUSE
trimmer
On completion of the opening step, the gate remains open. It is necessary to
instruct closure with another START command
Any START command issued during opening is ignored
Any START command issued during opening is accepted
Start during opening causes closure.
Start during closure causes opening.
Commands subsequent to starting cause, in order:
g
g
g
open
stop
close
stop...
At the end of each opening and closing step, the motors slow down in order
to avoid noisy closure and bouncing.
At the start of each opening and closing step, the motors are started at
maximum power
The time used for opening or closure will always be the value set by the WORK
trimmer, even if the previous operation has been interrupted before the expiry
of such time.
When an opening (or closing) operation is interrupted before expiry of the
set time (for example due to the intervention of one of the safety devices or
due to a start command), the duration of the subsequent closing (or opening)
operation will not be that set by the WORK trimmer, but will be equal to the
time effectively elapsed, plus a short supplemental time in order to compensate
for the inertia of the gate.
Intervention of the photocell during opening or closing causes the gate to
stop. When the photocell restores, the gate re-opens completely.
Intervention of the photocell during opening is ignored. Intervention of the
photocell during closing causes the gate to re-open completely.
The control unit performs a photocell operational test before starting each
opening or closing operation. If the photocells are not operating correctly, the
gate does not begin to move and the light flashes for approx. 8 seconds.
PLEASE NOTE: connect the photocell TX correctly
Select this option if using conductive rubber edges with nominal resistance of
8K2.
Select this option if using standard edges with switch normally closed or
optical edges.
Intervention of the edge during opening or closing causes inversion of the
direction of movement in order to free the body that caused the edge to
intervene. The gate will be stopped after approx. 3 seconds.
Intervention of the edge during opening is ignored. Intervention of the edge
during closing causes the gate to be re-opened completely.
The control unit performs an operational test on the edges before starting
each opening or closing operation. If the edges are not operating correctly, the
gate does not begin to move and the light flashes for approx. 8 seconds.
DO NOT enable testing if conductive rubber edges are used or standard
edges are used without a suitable control unit for controlling function.
- 14 -