6 . Operating states and diagnosis: LED display, flashing codes
The diagnosis is transmitted via the serial inputs Serial IN Pin 7 (X1) and Pin 8 (X1) of the master.
Color
Function
Green Safe sensor function
OSSD input circuit available,
on
door closed
flashes
door opened
1 x
flashes
OSSD input circuit not available and
2 x
door closed
flashes
OSSD input circuit not available and
4 x
door opened
Blue
Guard locking function
off
magnet not actuated
on
door closed, locking force available
flashes
door closed,
1 x
locking force not reached
flashes
door opened, magnet actuated
2 x
Red
Fault diagnosis
off
no error present
on
internal device error
flashes
error safety outputs
1 x
flashes
error safety inputs
2 x
flashes
overvoltage or undervoltage
3 x
flashes
error door torn opened
4 x
flashes
temperature outside the
5 x
permitted range
flashes
wrong RFID actuator
6 x
flashes
configured B10D - value exceeded
8 x
flashes
synchronization error RFID
9 x
flashes
slave not dedected
10 x
Table 1: flashing codes when a LED is lit
36
Possible cause
- one previous door in the circuit open
- wiring error
- cable interruption
- door and one of the previous doors are opened
- wiring error
- cable interruption
- unit soiled
- alignment of the anchor plate not correct
- incorrect calibration
- magnet actuated and the door opened
- internal device error
- short circuit between safety outputs, against ground or
against +24 VDC
- short circuit between safety inputs, against ground or
against +24 VDC
- only one of the two safety inputs available
- wire break
- supply voltage was not within the defined limits
- The door was forcibly opened by exceeding the locking force - switch power supply off and on
- defined temperature range has been undercut or exceeded
- incorrect actuator in sensor detection zone
- value achieved for replacement of connected relay module
(user-programmed)
- error during teach-in of the RFID
- wire break
- not connected
- device defective
Possible remedy
- close all doors
- connect pin 2 and pin 6 to +24 V
- or connect the output signals of the previous process lock
- close all doors
- connect pin 2 and pin 6 to +24 V
- or connect the output signals of the previous process lock
- clean HOLDX and the anchor plate
- check alignment of HOLDX to the anchor plate
- recalibrate with HOLDX-Manager
- close the door
- switch power supply off and on
- in case of recurrence return to supplier
- switch off the power supply
- repair the short-circuit at the output
- apply again the supply voltage
- switch off the power supply
- repair the short-circuit at the input
- apply again the supply voltage
- switch off the power supply
- ensure the correct power supply and apply the power supply again
- switch off the power supply
- ensure correct ambient temperature
- apply again the supply voltage
- use correct actuator
- Check or replace connected relay module. Reset B10D - value.
- contact SSP Support
- check cable connection
- check device