8.1

Address

8.2

Baud rate

Siemens Building Technologies
Fire Safety & Security Products
The address is set using switch elements S1 to S4 of the DIP switch SW1.
The switch elements S5 to S8 are not used (must be set to "OFF").
8-way dip switch
SW1
S1-S4
The address is set using binary code. "1" means the switch is in "ON"
position, "0" means "OFF" position.
Default setting
1000= address 1
0100= address 2
1100= address 3
0010= address 4
1010= address 5
0110= address 6
1110= address 7
0001= address 8
Address configuration
Tab. 5
The baud rate is set using dip switch SW2.
The baud rate to SISTORE MX is set using switch elements S3 and S4.
The switch elements S1 and S2 are not relevant.
The switch elements S5 to S8 must always be set to "OFF".
ON
4
3
1
2
5
OFF
8-way dip switch
SW2
S3
0
1
Default setting
0
1
SW2: Baud rate of SISTORE MX
Tab. 6
Switch positions that are not expressly mentioned are not supported!
Whenever the position of the dip switches is changed, the MX Multi-Channel Box must be reinitialized
by power off/power on.
6
7
8
S4
0
0
1
1
Setup
Baud rate
19200 baud
38400 baud
57600 baud
115200 baud