Herunterladen Inhalt Inhalt Diese Seite drucken

Install The Drive On The Wall; Connect The Power Cables - ABB ACS880-01 Kurzanleitung Für Die Installation

Vorschau ausblenden Andere Handbücher für ACS880-01:
Inhaltsverzeichnis

Werbung

4 EN – Quick installation guide

Install the drive on the wall

See figures
A
and
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure
EN
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
DA
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
please consult the manufacturer's instructions. Note: Moisture inside the motor
DE
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
ES

Connect the power cables

FI
See figures D, E,
FR
1. Remove the front cover. IP21 units: Release the retaining clip with a screwdriver
(a) and lift the cover from the bottom outwards (b). Remove the cable entry box
IT
cover by undoing the mounting screw.
2. Attach the residual voltage warning sticker in the local language next to the
NL
control board top.
PT
3. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver (a). Knock out holes for the
RU
cables to be installed (b).
4. Cut adequate holes into the rubber grommets. Slide the grommets onto the
SV
cables. Prepare the cable ends. Slide the cables through the holes of the bottom
plate and attach the grommets to the holes.
TR
5. Ground the cable shields 360 degrees under the grounding clamps.
CN
6. Connect the twisted cable shields to the grounding terminals.
7. Connect the conductors of the input and motor cables. Tighten the screws.
8. Install the EMC shroud separating the input and output cabling if not installed yet.
9. Units with option +D150: Connect the conductors of the brake resistor cable to the
R+ and R- terminals.
10. Reinstall the shroud on the power terminals.
11. Secure the cables outside the unit mechanically.
B
on page 81.
G
on page 83. Measure the insulation resistance between
F
and H. Use symmetrical shielded cable for the motor cabling.