5.5 Analogue / Modbus Interface

5.5.1 Interface Communication Parameters
Supported protocol
Physical layer
Supported baud rates
Supported parities
Data bits
Stopp bits
Address range
Function codes
5.5.2 Register Overview
Register No.
30001
Error code
30002
Measured speed
30003
Measured power
30004
Operation mode
30005
Analogue input
30006
Firmwareversion
Output Registers (function codes: 03, 06, 16) read / write
40001
Reset
Wink
40002
Set speed
40003
Maximum speed
40004
Hidden functions
40005
Timeout communication
40006
Password
40007
New password (protected)
40008
New baud rate (protected)
40009
New parity (protected)
40010
Function
(protected)
40011
Operation mode
*The dry contact is closed, if:
0: Ready:
1: Ready AND Motor runs
Appendix
Modbus RTU
EIA-485
9600, 19200, 38400, 57600 bps
none, even, odd
8
1
1...247 (adjustable in hexadecimal numbers 0x01...0xF7)
04 – read input registers
03 – read output registers
06 – write single output registers
16 – write multiple output registers
Description
Input Registers (function code: 04) read only
error
contact*
device: no error
device: no error AND Motor runs (speed > 250min
Range
0...7
0...2000 rpm
0...2000 watts
0 = Analogue
1 = Modbus
0...1000
0...65535
1
2
0, 250...2000 rpm
0...2000 rpm
0...2000
0...655 s
0...65535
0...65535
0...3
0 = 9600
1 = 19200
2 = 38400
3 = 57600
0...2
0 = none
1 = odd
2 = even
0...1
0 = Ready
1 = Ready AND Motor
runs
0...1
0 = Analogue
1 = Modbus
Default settings
-
-
-
-
-
-
0
0
1000
0 (do not change)
0 (0 = function disabled)
1111
0
2
0
0
0
-1
)