3.5 Analogue Interface

3.5.1 Programming of Maximum Speed According to Connected Fan
The programming has to be done by „Reset-button" left beside the LEDs (see Appendix 5.4
for detailed maximum speed information).
Step
Press reset button longer than 5 sec
Programming of max. speed step numbers
of press to button = program index
Waiting time app. 5 sec
Check of steps by watching yellow LED
Programming is finished
Table 7: Programming EKE 05-00xx-5E-IA
3.5.2 Set the EC-Controller into Operation
Step
Action
1
Connect motor cable
2
Connect mains
3
Connect the analogue input
4
Set min-speed and max-speed to
the desired values using the 2
potentiometers
5
Use 0-5V, 0-10V or 10k
potentiometer for speed setting
3.5.3 Set the EC-Controller out of Operation
1. Way:
Step
1
Set max speed to "0"
2. Way:
Step
1
Set Speed to "0"
3. Way:
Step
1
Remove mains plug
Commissioning
Action
Action
Action
Response by EKE05
If programming mode is launched, red and
green LED flashing alternating and the drive
is being stopped
The yellow LED is lighting as soon as button
is pressed
Yellow LED shows program index by flashing
Red LED stops flashing
Condition
Mains not connected
Motor is already
connected
see Figure 8 to Figure 10
see Figure 8 to Figure 10
see Figure 8 to Figure 10
Condition
Motor running
set speed value > 0 rpm
Condition
Motor running
max speed > 0 rpm
Condition
Motor running
Expected Reaction
Green Ready-LED will
start flashing
Motor will start and
speed up to the set
value
Expected Reaction
Motor stops
Expected Reaction
Motor stops
Expected Reaction
Motor stops