5 Appendix

5.1 LONWORKS
In.
Name
Node Object, ID #0
0
nviRequest
SNVT_obj_request
1
nvoStatus
SNVT_obj_status
FFU Object, ID #1
2
nviSpeed
SNVT_rpm
3
nvoSpeed
SNVT_rpm
4
nviEnable
SNVT_lev_disc
5
nvoFfuStatus
SNVT_char_ascii
Configuration
6
nciMaxSpeed
SNVT_rpm
7
nciMinSpeed
SNVT_rpm
8
nciSndOnDelta
SNVT_rpm
9
nciMaxSndTm
SNVT_time_sec
10 nciMinSndTm
SNVT_time_sec
User specific
struct {
Speed
SNVT_rpm
11
FfuStatus
SNVT_char_ascii
Enable
SNVT_lev_disc
} nvoVisual
struct {
Address
unsigned int:7
12
R_W
unsigned int:1
Data
unsigned long
} nviParameter
struct {
Address
unsigned int:7
13
Error
unsigned int:1
Data
unsigned long
} nvoParameter
14 nciRestartDelay SNVT_time_sec
15 nciPWMLimit
SNVT_count
16 nciIFaktor
SNVT_time_sec
17 nciIMax
SNVT_count
18 nciIOffset
SNVT_count
nciSpeedSetDe
19
SNVT_time_sec
lay
20 nciGradLimit
SNVT_rpm
21 nciSamples
SNVT_count
22 nvoPower
SNVT_power
nciSndOnDelta
23
SNVT_power
Pwr
struct {
Speed
SNVT_rpm
FfuStatus
SNVT_char_ascii
24
Enable
SNVT_lev_disc
Power
SNVT_power
}nvoVisualPwr
25 nciRSpeed
SNVT_rpm
Table 12: LONWORKS
1) i ..input; o ..output; c ..input config
Appendix
®
Interface
Type
1)
i
-
o
-
i
0
o
0
i
0
o
0
c
1000 rpm
c
250 rpm
c
20 rpm
500
c
(50,0s)
100
c
(10,0s)
0
0
0
o
i
o
c
10 (1,0s)
0xE000
10 (1.0s)
300
0
150
(15.0s)
30 rpm
4
o
0
200
c
(20,0W)
0
0
0
0
o
c
0
®
network interface
Default
Description
Set value (rpm)
Actual value (rpm)
Start/stop
Error code
Maximum speed (rpm)
Minimum speed (rpm)
Speed change to trigger sending
Heartbeat control: cycl. sending of
nvoVisual
Minimum
time
heartbeats
=nvoSpeed
=nvoFfuStatus
=f(Statuswort.Bit1)
No function / not used, only present for downwardly
compatibility.
Wait time before start after power-
on
No function / not used, only present for downwardly
compatibility.
Actual power value
Power change to trigger sending
=nvoSpeed
=nvoFfuStatus
=f(Statuswort.Bit1)
=nvoPower
Send after
change
change/
heartbeat
change/
heartbeat
between
two
change/
heartbeat
change/
heartbeat
EN-29 of 38

Werbung

Kapitel

Inhaltsverzeichnis
loading

Verwandte Produkte für Nicotra Gebhardt EKE05-00 Serie

Diese Anleitung auch für:

Eke 05-0018-5e-ixEke 05-0040-5e-ix

Inhaltsverzeichnis