3 Commissioning

Warning
Connect motor cable first before connecting mains!
Do not disconnect motor cable before all operation indicators are extinguished!
Certain inverter parameter settings may cause the motor to start automatically
after mains connection.
The MaxSpeed Parameter must be configured accurately for motor overload
protection to operate correctly.

3.1 Status Display

Status LED
Function
®
Service LED
LON
(yellow)
indication
Analogue
programming
Error LED
Error
(red)
indication
Ready LED
Ready
(green)
indication
Table 6: Function of status LEDs
Commissioning
Indication
state
Flashing (approx. 1 sec)
OFF
Flashing
OFF
ON
Flashing
Alternately flashing with
Ready LED
Flashing (approx. 0.5 sec)
Flashing (approx. 1 sec)
OFF
Alternately flashing with
Error LED
Controller State
®
LON
node "unconfigured"
®
LON
node "configured online"
Counting Maximum speed index
No error
Error
Error Internal Communication
Wave function activated
Device ready (during speed change)
Device ready (speed at setpoint)
Device not ready
Wave function activated
EN-16 of 38