Herunterladen Inhalt Inhalt Diese Seite drucken

Ingeteam INGECON SUN 3Play Handbuch Für Montage Und Betrieb Seite 94

Vorschau ausblenden Andere Handbücher für INGECON SUN 3Play:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 5
Ingeteam
CAUTION
The strings connected to the unit's connectors must be electrically independent of each other. That is, there
must not be any strings with a current higher than that permitted separated into several connectors, as the
current distribution is never guaranteed.
The cabling used for the connection must have dimensions in line with current regulations in the country of
installation and according to the type of installation, connectors, and maximum current and voltage of the PV array.
The unit includes fuses in the PV+ inputs. If it is necessary to mount fuses on the PV inputs- these can be
mounted externally using standard references for the Sunclix family by Phoenix Contact.
The table below shows the recommended fuses by maximum string current together with the Phoenix Contact
references:
Maximum string power Impp
9 A
11 A
13 A
15 A
18 A
20 A
94
PV fuse-
Fuses recommended for PV-
Fuse
15 A
20 A
25 A
32 A
Phoenix Contact fuse reference
PV-PRO/M/F-200/F-1500/13
PV-PRO/M/F-200/F-1500/17
PV-PRO/M/F-200/F-1500/20
PV-PRO/M/F-200/F-1500/25