3.Reference ETS-Parameter

3.1 General
function
General Settings contains some useful functions, such as heartbeat, sending a power supply presence message, and remote-
reset by using a telegram.
The chart shows the dynamic range for this parameter:
ETS ‐text
Heartbeat Time
Reset Type
Delay Time to Send Object :
Power supply on
The following chart shows the objects that belong to general setting:
Number
Name
1
Heartbeat
2
Power supply on

3.2 Measurements

This menu contains three measurements, Output Voltage, Output Current and Device Temperature.
3.2.1 Output Voltage Measurement
This function can be used to monitor output voltage, sending values measured and rising alarm when the output is out of
the working range, 28V - 31V.
Dynamic range
[default value]
10 - 36,000S
[60s]
With 0
With 1
With 0 or With 1
No delay, 1min, 2min, 3min, 4min, 5min,
10min, 15min, 20min, 25min, 30min,
1hour, 2hours, 3hours, 4hours, 5hours,
6hours, 7hours, 8hours
[No delay]
Length
1
bit
1
bit
Comment
Heartbeat telegram is sent at regular intervals to
indicate that the power supply is working normally
Set types of telegram to trigger a remote reset to
restart the KNX but. NOTE: The device resets itself
automatically when it is in short circuit conditions for
10 secs
After returning to normal working condition, a telegram
is sent after this time delay to notify the power supply
is ready
Usage
Send a telegram of "1" to the system at regular intervals
when working normally
After initial startup or reset, a telegram of "1" will be sent
after a time delay you set via this object