Mean Well KNX-40E-1280D Bedienungsanleitung Seite 10

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ETS-text
Voltage Measurement
Voltage Object Type
Voltage Cyclic Sending
Voltage Alarm
Behaviour On Voltage Alarm Active
Behaviour On Voltage Alarm Deactive
The following chart shows the objects that belong to general setting:
Number
Name
11
Output voltage measured
12
Output voltage alarm
3.2.2 Output Current Measurement
This function can be used to monitor load conditions, sending current measured and rising alarm when values are higher
than the threshold.
Dynamic range
[default value]
Disable
Enable
4byte[DTP14]
2byte[DPT9]
OFF, 1min, 2min, 3min,
4min, 5min, 10min, 15min,
20min, 25min, 30min,
1hour, 2hours, 3hours,
4hours, 5hours, 6hours,
7hours, 8hours
[OFF]
Disable
Enable
Nothing to do
Send 0
Send 1
Nothing to do
Send 0
Send 1
Length
Usage
2bytes
The device sends the measured output voltage
value in V or mV at regular intervals.
4bytes
1 bit
When the measured value is out of the normal
working range a telegram with value 0 or 1 is
sent. When the measurement values return to
the normal range a telegram with value 0 or 1 is
sent.
Comment
Enable or disable voltage measurement
Select data point type
Send the latest voltage value at intervals you
desired
Enable or disable the alarm function
Select a reaction when there is abnormal voltage
Select a reaction after abnormal voltage is
removed
7