3.2.3 Device Temperature Measurement
This function can be used to monitor internal temperature of the device, sending values measured and rising alarm when
values are higher than the threshold.
ETS-text
Temperature Measurement
Temperature
Difference Sending
Temperature
Cyclic Sending
Temperature
e Alarm
Temperature
Threshold
Temperature
Hysteresis
Behaviour On Temperature Alarm
Active
Behaviour On Temperature Alarm
Deactive
Dynamic range
[default value]
Disable
Enable
OFF, 2
°C
, 3
°C
, 4
°C
, 5
°C
,
6
°C
, 7
°C
, 8
°C
, 9
°C
, 10
°C
[OFF]
OFF, 1min, 2min, 3min,
4min, 5min, 10min, 15min,
20min, 25min, 30min,
1hour, 2hours, 3hours,
4hours, 5hours, 6hours,
7hours, 8hours
[OFF]
Disable
Enable
0-100°C
[70
°C
]
0-40°C
[1
°C
]
Nothing to do
Send 0
Send 1
Nothing to do
Send 0
Send 1
Comment
Enable or disable temperature measurement
Difference between actual and last sent value
which triggers the sending
Send the latest voltage value at intervals you
desired
Enable or disable the alarm function
Select a threshold value to perform the Behaviour
on Temperature alarm
Active"
Select a hysteresis value to perform the Behaviour
on Temperature alarm
Deactive"
Select a reaction when temperature is higher than
Temperature Threshold
Select a reaction when temperature is lower than
value of
"Temperature Threshold"
Hysteresis", e.g.
70°C -1°C = 69°C
"
"