Device
15
2bytes
temperature
measured
Device
temperature
16
1bit
alarm
2bytes
Maximum
output current
17
2bytes
during tracking
period
4bytes
Maximum
device
18
2bytes
temperature
during tracking
period
Busload
19
1byte
measured
20
Busload alarm
1bit
The number
21
of overload
2bytes
times
Overload
22
4bytes
duration
The number
of short
23
2bytes
circuits times
Time load
24
4bytes
detached
25
Alarm 1
1bit
26
Count 1
2bytes
27
Duration 1
4bytes
28
Alarm 2
-----
31
Alarm 3
-----
34
Alarm 4
-----
temperature
,°C
CRT
(DPT=9.001)
alarm
CRT
(DTP = 1.005)
current,mA
(DPT=7.012)
current,mA
CRT
(DPT=9.021)
electric current,A
(DPT=14.019)
temperature
,°C
CRT
(DPT=9.001)
percentage,
0~255%
CRT
( DPT=5.004)
alarm
CRT
(DTP = 1.005)
Pulses
CRT
(DPT = 7.001)
Pulses
CRT
(DPT = 7.001)
Pulses
CRT
(DPT = 7.001)
time lag(s)
CRT
( DPT=13.100)
Alarm
CRT
(DTP = 1.005)
Pulses
CRT
(DPT = 7.001)
time lag(s)
CRT
( DPT=13.100)
The device sends the measured device temperature
Measurement
value in
°C
at regular intervals.
When the measured value is above the threshold a
telegram with value 0 or 1 is sent. When the
measurement values return to the normal range
Alarm
(less than the hysteresis) a telegram with value 0
or 1 is sent.
The device sends the measured output current
Measurement
value in A or mA at the end of each period.
The device sends the measured device
Measurement
temperature value in
The device sends the measured Bus load
Measurement
value in % at regular intervals [0-255%]
When the measured value is above the threshold
a telegram with value 0 or 1 is sent. When the
Alarm
measurement values return to the normal range
(less than the hysteresis) a telegram with value 0
or 1 is sent.
The device sends the number counted value of
Analysis
overload at regular intervals.
The device sends the total duration time in
Analysis
overload in second
The device sends the number counted value of
Analysis
short circuit at regular intervals.
On activation the device sends the time counter
Analysis
value of load detachments
When the measured value is above/below the
threshold a telegram with value 0 or 1 is sent. When
the measurement values return to the normal range
Group Alarm
(less/higher than the hysteresis) a telegram with
value 0 or 1 is sent.
The device sends the number counted value of
threshold events for output current, output voltage
Group Alarm
or device temperature.
The device sends the total duration time
(in second) for output current, output voltage or
Group Alarm
device temperature.
°C
at the end of each period.
5