3.7 Customized Alarm 1-4

"
Customized Alarm provides alterable measurements for users. With these adjustable measurement sources, users can easily
"
build their preference settings for purposes.
ETS ‐text
Alarm Function
Measurement Source
Threshold Setting
Hysteresis Setting
Alarm Type
Behavior On Alarm
Active
Behavior On Alarm
Deactive
Dynamic range
[default value]
Disable
Enable
Output Current
Device Temperature
Output Voltage
10-1600mA
[1280mA]
40-95°C
[70
°C
]
28-32V
[31V]
10-1280mA
[10mA]
5-90°C
[5
°C
]
1-6V
[5V]
Limit Undercut
Limit Exceeded
Nothing to do
Send 0
Send 1
Nothing to do
Send 0
Send 1
Comment
Enable or disable Alarm Function
Selection of the measurement source
Select a threshold value to perform the Behavior On
Alarm
Active"
Select a hysteresis value to perform the Behavior
On Alarm
Deactive"
Select threshold region either to lie above
(limit exceeded) or to lie below (limit undercut) the
threshold value
Select a reaction when detected value is higher/ lower
than the Threshold
Select a reaction when detected value is lower/ higher
than
a value of
"Threshold Setting" - "Hysteresis Setting",
e.g. 1280mA - 10mA = 1270mA
"
"
15