2.10
P menus for the user
A summary of all the accessible P-menus is given
below.
Menu P1 > Status of time programmes
Submenu
Description
P11
Is menu P21 currently active?
P12
Is menu P22 currently
active?
P13
Is menu P23 currently
active?
P14
Is menu P24 currently active?
P15
Is menu P25 currently active?
P16
Is menu P26 currently
active?
Menu P2 > Setting time delays
Submenu
P21
Only applies to systems
fitted with two SA 1-3V, SA
0-3V or SAI Flash switches.
P22
Only applies to systems
fitted with two SA 1-3V, SA
0-3V or SAI Flash switches.
P23
Only applies to systems
fitted with a SA 1-3V, SA
0-3V or SAI Flash switch.
P24
P25
Only applies to systems
fitted with an RFZ swith.
P26
Only applies to systems
fitted with an RFZ swith.
P27
EN - 12
Status
Activated
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Description
Delay timer for the bathroom switch (to switch to high
position).
'x' minutes after operating the bathroom switch,
■
the unit switches to the high setting.
Overrun timer for the bathroom switch (to switch to normal
position).
'x' minutes after operating the bathroom switch, the unit
■
switches back to the normal setting.
Overrun timer for ventilation position 3 (using a hardwired
3-position switch).
If ventilation setting 3 (high) is switched on briefly
■
(< 3 sec), the unit will switch to the high setting for 'x'
minutes and then automatically returns to the
normal setting.
If any switch is operated during this lagging time the unit will
instantly revert to the ventilation position as set at that time.
Filter warning
'x' weeks after cleaning the filters the "filter dirty" alert
■
will reappear.
Overrun timer for ventilation setting 3 (using
After pressing
briefly (< 2 sec.), the unit will switch
■
to the high setting for 'x' minutes and then automatically
returns to the normal setting.
If any switch is operated during this lagging time the unit will
instantly revert to the ventilation position as set at that time.
Overrun timer for ventilation setting 3 (using
After pressing
continously (> 2 sec.), the unit will
■
switch to the high setting for 'x' minutes and then
automatically returns to the normal setting.
If any switch is operated during this lagging time the unit will
instantly revert to the ventilation position as set at that time.
n/a
Menu P9 > Status of additional programmes
Submenu
Description
P90
Open fire programme active?
P91
Bypass open?
P94
Analogue input (0-10V)
active?
P95
Frost protection active?
P96
n/a
P99
Enthalpy programme active?
Time delay values
Minimum
0 Min.
0 Min.
0 Min.
10 weeks
1 Min.
).
1 Min.
).
0 Min.
Status
Activated
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Yes (1) / No (0)
Maximum
General
reset
15 Min.
0 Min.
120 Min.
30 Min.
120 Min.
0 Min.
26 weeks
16 weeks
20 Min.
10 Min.
120 Min.
30 Min.
120 Min.
30 Min.