BTL5-P1-M_ _ _ _-B/Z-DEX_-K_ _/KA_ _
Micropulse Transducer - Rod Style
3
Installation (cont.)

3.3.1 Transducer installation

The transducer is threaded directly
into its holder.
The installation surface of the
BTL housing must lie fully
against the mating surface. The
appropriate O-ring must seal the
bore hole perfectly, i.e. the
chamfer for the O-ring must be
finished according to ➥ ➥ ➥ ➥ ➥ Fig. 3-4.
Suitability of the installed O-ring
(Viton GFLT90) must be verified
for the specific application.
The depth of the threaded hole
must be at least 25 mm.
At least 5 threads must be en-
gaged and there must be a
thread overlap of at least 8 mm.
Zone 1
dividing area
Zone 0
aaaaaaaaaaaa
Stop,
1.4301
Cotter pin
DIN 94 – 3.2 × 20 – 1.4301
➥ ➥ ➥ ➥ ➥ installation note!
Fig. 3-6: Direct transducer installa-
tion

3.3.2 Floats, installation

Only the floats called out here may
be used for level sensing in Zone
0. ➥ ➥ ➥ ➥ ➥ Figs. 3-7 to 3-10.
Each float is designed so that it
makes electrical contact with the
transducer rod in any orientation.
Therefore:
Observe the prescribed
installation orientation
exactly!
The immersion depths s
for a liquid density of 1 g/cm
well as for a density of 0,7 g/cm
➥ ➥ ➥ ➥ ➥ Table 3-1.
In order to measure the position of
the separating layer between two
fluids, e.g. oil and condensed
water, a second float can be em-
ployed. Suitale:
BTL2-S-4414-4Z01-Ex.
Installation orientation:
Cylindrical part is top side of float
Fig. 3-7: BTL2-S-6216-8P-Ex
Float in Zone 0 (optional)
Immersion
depth s
s
of float
➥ ➥ ➥ ➥ ➥ Table 3-1
Float Type
BTL2-S-6216-8P-Ex
BTL2-S-5113-4K-Ex
BTL2-S-4414-4Z-Ex
BTL2-S-4414-4Z01-Ex
Table 3-1: Immersion depths s
Flameproof enclosure
Installation
orientation:
Raised mark-
ing on top
side of float
Fig. 3-8: BTL2-S-5113-4K-Ex Float
in Zone 0 (optional)
are given
s
3
as
3
.
Installation
orientation:
Raised mark-
ing on top
side of float
Fig. 3-9: BTL2-S-4414-4Z-Ex Float
in Zone 0 (optional)
Installation
orientation:
2 raised mark-
ings on top
side of float
Fig. 3-10: BTL2-S-4414-4Z01-Ex
Special float in Zone 0 (optional)
min. density
1 g/cm
0.6 g/cm
3
s
~ 41 mm
s
0.7 g/cm
3
s
~ 26 mm
s
3
0.7 g/cm
s
~ 30 mm
s
3
0.85 g/cm
*
s
~ 45 mm
s
* Density of the float
s
Ignition Class "d"
3
(H
O)
0.7 g/cm
3
2
s
~ 57 mm
s
s
~ 40 mm
s
s
~ 39 mm
s
sinks
english
7